UKH Journal of Science and Engineering | Volume 5 • Number 1 • 2021 73
Contingency Analysis and Ranking of Kurdistan Region
Power System Using Voltage Performance Index
Ali Abdulqadir Rasool
1,a*
, Najimaldin M. Abbas
2,b
, Kamal Sheikhyounis
3,c
1,3
Department of Electrical Engineering, College of Engineering, Salahaddin University-Erbil, Erbil, Iraq
2
Department of Electrical Engineering, College of Engineering, Kirkuk University, Kirkuk, Iraq
E-mail:
a
ali.rasool@su.edu.krd,
b
dralbyati@uokirkuk.edu.iq,
c
younis@ieee.org
1. Introduction
Contingency can be expressed as an undesirable event happening in the power system network such as an outage of
one or more components of the power system for example loss of a transmission line (Fischl, Halpin et al. 1982). During
the outage of any equipment, contingency study displays an idea of what may be the situation of the power system after
the contingency occurrence (Doshi, Salgar et al., 2015). In order to confirm the reliability of the system, contingency
study is accomplished as part of the power system operation and planning. It could help utilities in identifying possible
problems, arranging helpful measures beforehand, making right choices for maintenance purposes, and taking improved
control arrangements (Ruiz & Sauer 2007). In this paper, analysis and variations in the voltage profile for the whole
system after the occurrence of the transmission line outage are presented.
This analysis provides more confidence in the security of the power system beyond the contingency occurrence in a
bulk power system to enhance voltage stability (Muhammad 2019). The outage of one branch of transmission line may
lead to a line overloading in other branches and/or a system voltage rise or drop. Load flow analysis using Newton
Raphson is the useful approach for study and analysis. Bus voltages after all possible line outages are calculated and
recorded. Transmission line contingency severity is evaluated using voltage the Performance Index PIv. The highest
value of this index means the highest severity of the contingency (Chowdhury, Mondal et al., 2015).
2. Study Description
A real 132 kV power system of KR network is shown in Figure 1 which consists of 280 buses, 123 loads and 284
branches with total power generation of 3535.0513 MW and 3455.6566 MW as peak load for the month of July 2020.
Access this article online
Received on: December 16, 2020
Accepted on: January 25, 2021
Published on: June 30, 2021
DOI: 10.25079/ukhjse.v5n1y2021.pp73-79
E-ISSN: 2520-7792
Copyright © 2021 Ali et al. This is an open access article with Creative Commons Attribution Non-Commercial No Derivatives License 4.0 (CC BY-
NC-ND 4.0)
Research Article
Abstract
In this paper, analysis and ranking of single contingency due to the outage of transmission lines for a large scale
power system of the Kurdistan Region (KR) are presented. Power System Simulator software (PSS®E33) is used to
simulate the Kurdistan Region power system network and perform the contingency analysis for single line outage.
This analysis is essential in order to predict and evaluate the voltage stability in case of contingency occurrence to
know the most severe case and plan for managing it. All possible transmission line outages of the network are tested
individually. After each branch disconnects, load flow analysis are applied by using Newton Raphson method then
all bus voltages are recorded, and compared with them before the contingency. Voltage performance index is
calculated for all possible contingencies to rank them according to their severity and determine the most severe
contingency which is corresponding to the highest value of performance index. Also, the contingencies which cause
load loss and amount of this load are observed.
Keywords: Voltage Stability, Contingency Analysis, PSS®E33, Voltage Performance Index (PIV),
Kurdistan Region (KR) Network.
UKH Journal of Science and Engineering | Volume 5 • Number 1 • 2021 74
Figure 1. Kurdistan Region Network.
Figure 2 shows the voltage profile of the system buses without any contingency as it is clear some buses are under
minimum permissible range (0.9 pu). The average bus voltages without contingency is 0.95455.
Figure 2. Voltage Profile for KR Network Buses without Contingency.
The contingency study includes single line outage only. All possible contingencies are simulated and the bus voltages
are recoded under each contingency then the voltage performance index is calculated for each contingency. The
UKH Journal of Science and Engineering | Volume 5 • Number 1 • 2021 75
permissible voltage range is 132 kV ± 10% according to the Iraqi Grid Code (Husein & AbdulFatah 2016). The voltage
performance index is ranked to determine the most severe transmission line outage.
Many important files are needed to be used as input files for PSS®E which are:
1) Saved case file (*.sav): contains the information about the content of power system networks such as buses,
branches, power plants and loads.
2) Subsystem file (*.sub): creates a subsystem for studying and analyzing in a given area.
3) Monitoring data file (*.mon): monitors the elements of the network to record the bus voltages less than or
higher than permissible voltage, and it records the power flow rate with higher than 100% of the full capacity.
4) Contingency file (*.con): all contingencies with voltage and power flow rate violation are recorded.
The contingency report consists of four parts: general data, branches with power flow violation and the percent of
violation, bus voltage with lower than or higher than permissible voltage change and the fourth part is the contingency
legend.
3. Newton Raphson Method for Load Flow
The power flow analysis is one of the most important problems in power system studies (Milano 2008). The most useful
method for load flow is Newton Raphson due to its advantages and accuracy (Roy & Jain 2013). Power flow solution
is the fundamental duty of power system operation. The following equations illustrate the Newton Raphson load flow
technique (Okakwu, Ogujor et al., 2017).


(1)
Where I
i
is the current injected into the bus i, writing the equation polar form





(2)
The current in terms of of active and reactive power at bus i:

(3)
From these two above equations we get:



󰇛

󰇜

(4)
By separating real and imaginary parts


󰇛

󰇜

(5)


󰇛

󰇜

(6)
These two equations can be rewritten as:

󰇛󰇜

󰇛󰇜

󰇛󰇜

󰇛󰇜

󰇛󰇜


󰇛󰇜



󰇛󰇜


󰇛󰇜


󰇛󰇜


󰇛󰇜



󰇛󰇜


󰇛󰇜


󰇛󰇜

󰇛󰇜



󰇛󰇜

󰇛󰇜

󰇛󰇜

󰇛󰇜



󰇛󰇜

󰇛󰇜

󰇛󰇜

󰇛󰇜

󰇻
󰇛
󰇜
󰇻

󰇻
󰇛
󰇜
󰇻
(7)
This matrix can be written as:


(8)
Where J
1
, J
2
, J
3
and J
4
are Jacobian sub matrices.
For J
1
diagonal element:







(9)
For J
1
off diagonal element:




(10)
For J
2
diagonal element:










(11)
For J
2
off diagonal element:
UKH Journal of Science and Engineering | Volume 5 • Number 1 • 2021 76


󰇛

󰇜 (12)
For J
3
diagonal element:








(13)
For J
3
off diagonal element:






(14)
For J
4
diagonal element:












(15)
For J
4
off diagonal element



󰇛

󰇜 (16)
The difference between scheduled and calculated values are 
󰇛󰇜
and 
󰇛󰇜

󰇛󰇜

󰇛󰇜
(17)

󰇛󰇜

󰇛󰇜
(18)
The solution for the new values of the voltage and angle are:
󰇛󰇜
󰇛󰇜

󰇛󰇜
(19)
󰇛󰇜
󰇛󰇜

󰇛󰇜
(20)
4. Voltage Performance Index
The usual way for checking the steady state contingency is by running the load flow for the system after each line outage.
Some line outages could result in the constraint violations of the system such as bus under and over voltages and
transmission line overload. The system performance regarding bus voltages can be evaluated by an index which identifies
the severity limit of voltage values as a result of a given contingency (Swarup & Sudhakar 2006).
The ranking of the system is done by sorting the contingencies according to the values of performance index, below
is the equation of this index (Semitekos & Avouris 2002).

󰇣
󰇛


󰇜



󰇤

(21)
Where Vi is the voltage of bus i
Vmax and Vmin are maximum and minimum voltage limits.
Vinorm is the avearge of maximum and minimum voltage.
N is the number of system buses.
5. Contingency Analysis and Ranking Algorithm
There is growing need to give the operators the essential information regarding security level of the system as a result
of the contingencies in the power system and to know what measures should be chosen, or not chosen (Chen &
McCalley 2005;,Donde, López et al., 2008). In light of this fact, it is important to rank the contingencies according to
their severity. Figure 3 is the flow chart for the contingency analysis and ranking.
6. Results
The process of a single contingency for a large scale power system of KR is simulated using PSS©E software and all
transmission line outages were tested individually. Newton Raphson load flow was conducted after each line outage
then all bus voltages were recorded and the voltage profile for the whole system ws observed. Figure 4 shows the voltage
profile for the most severe cases which are the outages of the lines (14001-14003) 1 and (14001-14003) 2 as it is clear
the voltage profile is worse than that of the system without any contingency as shown in Figure 1 and the average bus
voltages is less than that of normal case without contingency.
Figure 5 illustrates the amount of load loss during single contingencies. It is clear that the outage of line (341-13036) 1
causes the greatest load loss which is 52.4 MW. The remaining contingencies do not cause load loss in the network.
The voltage performance index was calculated for each contingency using equation (21) then these values were
recorded and ranked in a descending manner. The highest value represents the severest transmission line outage. Due
to the large number of contingencies only the first twenty contingencies are listed in Table 1. It is clear that the outage
of lines (14001-14003) 1 and (14001-14003) 2 have the highest voltage performance index which is 114.305 so it is the
most severe contingency. It was also observed that this line outage has the highest number of buses suffering from
voltage violation (voltages below minimum permissible value 0.9 pu) which are 26 buses and also it has the lowest
average bus voltage which is 0.94701.
UKH Journal of Science and Engineering | Volume 5 • Number 1 • 2021 77
Figure 3. Flow Chart of Contingency Analysis and Ranking.
Figure 4. Voltage Profile for KR Network Buses with Severest Contingency.
UKH Journal of Science and Engineering | Volume 5 • Number 1 • 2021 78
Figure 5. Amount of Load Loss at Single Contingencies.
Figure 6 shows the voltages of all these 26 buses for pre contingency and post contingency in case of the severest line
outage. The figure shows the effect of the severest case of line outage on the bus voltages which proves that the highest
voltage performance index values means the most severe line outage.
Table 1. Voltage Performance Index Ranking.
Contingency (Line
Outage)
Voltage Performance Index
Contingency
Ranking
14001-14003)1
114.305498
1
14001-14003)2
114.305498
14003-14018)1
107.782158
2
14003-14018)2
107.782158
601-1303
105.501761
3
1434-14020
99.60087
4
402-1302
99.268291
5
10-601
98.691466
6
13026-14020
98.57855
7
1345-13040
98.126742
8
1434-13026
97.330376
9
10-1305
97.087836
10
1354-13036
96.364338
11
103-1345
95.688988
12
103-13004
95.386994
13
13019-13036
95.371594
14
1312-13013
94.942615
15
402-1308
94.865219
16
1305-1306
94.591238
17
1354-13019
93.843274
18
(10012-10029)1
92.460509
19
(10012-10029)2
92.460509
14018-14020
91.576225
20
UKH Journal of Science and Engineering | Volume 5 • Number 1 • 2021 79
Figure 6. Minimum Bus Voltages Pre and Post (14001-14003) outages.
7. Conclusions
Single contingencies for the KR network are analyzed and ranked according to their severity by using PSS®E software.
All possible single contingencies are simulated and Newton Raphson load flow is applied after each contingency then
voltages of all buses are recorded to observe the voltage profile of the network for each case.
Contingency ranking is obtained by calculating the voltage performance index for each contingency and ranking them
from the highest to lowest value. It was found that the outages of the lines (14001-14003) 1 and (14001-14003) 2 have
the highest index value (114.305) which is the most severe contingency. This is validated also by observing the average
and minimum bus voltages. It was found that the highest index value corresponds to the lowest average and minimum
bus voltage. This evaluation of the most severe contingency is used in the operation and planning process to estimate
the situation and prepare the required measures in advance.
References
Chen, Q. & J. D. McCalley (2005). Identifying high risk Nk contingencies for online security assessment. IEEE
Transactions on Power Systems, 20(2): 823-834.
Chowdhury, A. K., et al. (2015). Voltage security assessment of power system. World Scientific News, 21, 83-97.
Donde, V. et al. (2008). Severe multiple contingency screening in electric power systems. IEEE Transactions on Power
Systems, 23(2), 406-417.
Doshi, V. et al. (2015). Latest Trends In Contingency Analysis of Power System. International Journal of Innovations in
Engineering Research and Technology, 2, 1-11.
Fischl, R. et al. (1982). The application of decision theory to contingency selection. IEEE Transactions on circuits and
systems, 29(11), 712-723.
Milano, F. (2008). Continuous Newton's method for power flow analysis. IEEE Transactions on Power Systems, 24(1), 50-
57.
Muhammad, T. K. (2019). Performance improvement of interconnected 400kV, 50Hz Kurdistan and Iraq power
systems using proposed HVDC link. ZANCO Journal of Pure and Applied Sciences, 31(s3), 131-136.
Okakwu, I. K., et al. (2017). Load Flow Assessment of the Nigeria 330-kV Power System. American Journal of Electrical
and Electronic Engineering, 5(4), 159-165.
Roy, A. K. & S. K. Jain (2013). Improved transmission line contingency analysis in power system using fast decoupled
load flow. International Journal of Advances in Engineering & Technology, 6(5), 2159.
Ruiz, P. A. & P. W. Sauer (2007). Voltage and reactive power estimation for contingency analysis using sensitivities.
IEEE Transactions on Power Systems, 22(2), 639-647.
Semitekos, D. & N. Avouris (2002). Power Systems Contingency Analysis using Artificial Neural Networks. Proceedings of the
4th international workshop on computer science and information technologies CSIT.
Swarup, K. S. & G. Sudhakar (2006). Neural network approach to contingency screening and ranking in power systems.
Neurocomputing, 70(1-3), 105-118.